The 3,000 MW question for European solar
An attacker would theoretically need control of less than 1% of Europe’s installed solar capacity to potentially trigger a major grid disturbance, highlighting a significant and growing cybersecurity risk for the energy sector. While EU regulations still leave critical gaps, solar asset owners can reduce their exposure today through stronger network segmentation, secure remote access, robust authentication, controlled firmware updates and outbound-only communication.
Last August 27, Chile’s National Electric Coordinator recorded the forced disconnection of the 103 MW Huatacondo solar park and its 98 MW / 312 MWh battery energy storage system, after the plant’s control center reported a cyberattack on the facilities. Two months later, the coordinator’s daily reportSource: Ini, L. (2026, October 29). Chile solar and battery system remain offline after cyberattack. Energy Storage. still listed both installations under forced outage, with 0% availability.
Chile is far from home, but Europe has had its own warnings this autumn.
In early October, the Smart Energy Expert Group (SEEG) working group on cybersecurity published its recommendations to address cybersecurity risk in photovoltaic generation.Source: Smart Energy Expert Group. (2026, October 1). Recommendations to address cybersecurity risks in photovoltaic generation (Version 1.1) [Report]. European Commission. Then, a few days later, the AIVD and MIVD (Dutch intelligence services) published an advisory with NCSC-NLSource: Algemene Inlichtingen- en Veiligheidsdienst & Militaire Inlichtingen- en Veiligheidsdienst. (2026, October 7). Cyberadvies: Edge devices structureel doelwit van Chinese cyberactoren [Cyber advisory]. Ministerie van Binnenlandse Zaken en Koninkrijksrelaties. warning that Chinese cyber actors increasingly target edge devices (the firewalls, VPN gateways, proxies and portals that connect a network to the internet) and that attacks through such devices are expected to strongly increase in the coming years.
So we wondered how much capacity attackers would need to control to severely impact the European system. SolarPower EuropeSource: SolarPower Europe (2025). Solutions for PV cyber risks to grid stability [Report]. puts a number on it: 3,000 MW.
In this piece, we want to uncover what this number means, see how the EU law still falls short, and what asset owners can (and should!) do without waiting for the next law change.
What if 3,000 MW disappeared at once?
Continental Europe’s TSOs have a frequency containment reserve (FCR) to cover a reference incident of 3,000 MWSource: European Network of Transmission System Operators for Electricity. (2018, March 13). Explanatory note for the FCR dimensioning rules proposal [Supporting document]. in either direction. This reserve responds automatically to an imbalance and keeps the system’s frequency near 50 Hz until slower restoration reserves (aFRR, mFRR…) take over.
An imbalance larger than the available reserve could push the grid frequency outside of its safe range. In that case, TSOs will start disconnecting load or generation in a controlled way; if those measures are insufficient, the situation can escalate into wider-scale outages.
But 3,000MW of reserve is a lot… right?
If we look at the numbers, we can see that solar became big enough to highly matter. According to SolarPower Europe,Source: SolarPower Europe. (2025, December 11). EU solar market outlook 2025–2030 [Report]. EU installed PV capacity grew from 86 GW in 2015 to 406 GW in 2025 (a 372% increase!), and is projected to reach 718 GW by 2030.
So, to exceed 3,000MW, an attacker would theoretically need simultaneous control of less than 1% of Continental Europe's installed base.After excluding EU systems outside that synchronous area and adding the non-EU systems synchronised with it, the relevant installed PV base is still on the order of 400 GW.
How can an attacker reach a solar park?
In its recommendation report,Source: Smart Energy Expert Group. (2026, October 1). Recommendations to address cybersecurity risks in photovoltaic generation (Version 1.1) [Report]. European Commission. the SEEG divides solar installations into four size classesNamely: plug-in, residential, commercial/industrial, and utility-scale. and maps five primary attack vectors.Namely: manufacturer cloud portals, local networks, installers/maintenance providers, aggregators, and backdoors. The different classes have different risk levels for each exposure point.
For instance, at a residential and C&I scale, the primary exposure point comes from the manufacturer cloud portal, because a single platform can manage tens of gigawatts.
As they are usually not connected to those platforms, that path is less risky for utility-scale plants (>1MW). Instead, the SEEG identifies two other high-risk paths for them:
- Vulnerabilities in equipment hardware or firmware: Weaknesses introduced during production or through firmware update pipelines, which malicious actors can exploit. As they sit in the equipment itself, they remain reachable even if a plant is isolated from external platforms, and the same weakness repeats across every site running on that same equipment line.
- Intrusions through the plant’s local communication network: Attackers first compromise remote-access firewalls, unsegmented field networks, or VPN concentrators, then use poor network segmentation to move laterally from one system to the next.
This second type of attack scales because owners and service providers often reach many sites through similar remote-access arrangements. One break-in could therefore put more than 3,000 MW within reach.
Poland gave a clear example in December 2025. CERT Polska documentedSource: CERT Polska. (2026). Energy sector incident report – 29 December [Incident report]. NASK. that attackers entered 30+ wind and solar farms through internet-exposed FortiGate devices functioning as both firewalls and VPN concentrators. In affected plants, the VPN interface was accessible from the internet, and authentication wasn’t protected by MFA. After gaining access to the site networks, the attackers used default credentials to damage remote terminal units, serial device servers, some protection-and-control relays, and local operator interfaces at grid-connection substations.
The CERT’s follow-up reportSource: CERT Polska. (2026, August 8). Follow-up analysis of the 29 December 2025 energy sector incident [Report]. showed the attackers went further. From one wind farm, they moved through a cellular router into a private mobile network access point name (APN) run by the DSO, where devices can communicate with one another. This allowed the attackers to reach a separate CHP plant and shut down its steam turbine and water-treatment system. CERT Polska says that, to the best of its knowledge, this “was the first observed instance of this attack vector being used in a real‑world cyberattack”.
Power generation continued, but operators lost both visibility and the ability to receive DSO commands.
None of the individual weaknesses was new. Poor segmentation, poor credential management and poor vulnerability management combined into one attack path across several sites. So we have our lesson: basic cyber hygiene and safe network architecture would have strongly reduced the likelihood and impact of this type of attacks, and can buy time to both detect and contain the attacks that actually succeed.
What about the European rules?
The legal gap analysis in the SEEG report details why current European frameworks do not prevent these exposures. Three specific gaps affect utility-scale solar generation:
1. The CRA lets inverter manufacturers “grade their own homework”
Under the Cyber Resilience Act, inverters are products with digital elements, but aren’t classified as “important or critical”. Manufacturers can therefore claim conformity compliance through internal control without involving an independent notified body. Moreover, the CRA’s requirements only apply to products placed on the market from the 11th of December 2027, leaving the already installed base outside of that regime.
Market surveillance authorities can still examine products that present a significant risk, but they evaluate them against requirements written mostly for accidental vulnerabilities. The SEEG warns that it might not be an effective way to find vulnerabilities such as a deliberate backdoor.
2. The grid code checks only how a plant behaves, not who can reach it
The Requirements for Generators (RfG) mandates that plants above 1 MW (category B)Note that some national grid codes set lower Type B cutoffs and extend remote telecontrol and reactive-power requirements across categories. must provide a telecontrol interfaceSource: European Commission. (2016, April 14). Commission Regulation (EU) 2016/631 of 14 April 2016 establishing a network code on requirements for grid connection of generators (Text with EEA relevance). Official Journal of the European Union, L 112, 1–125.
See Article 14 (b). for the grid operator to connect to. The operational notification procedure checks connection behavior (including frequency response and reactive-power capability), but does not directly include cybersecurity requirements.
A plant can therefore pass all compliance tests while using a default password on its remote-access gateway. The SEEG notes that, where national law allows, grid operators can already add security requirements to that procedure.
3. Split architectures mask update origins
Vendors may host their monitoring dashboards on EU servers while running firmware updates, signing infrastructure, and command channels from countries presenting cybersecurity risks. This means that the parts that decide which code runs on the inverter still sit outside EU jurisdiction, and a data residency clause in a supply contract will miss them unless it names the signing keys and the update servers.
What the working group recommends
The SEEG proposes specific mitigations for utility-scale plants:
- Classify PV inverters as Class II important productsClass II (unlike Class I) keeps the notified body involved even once a harmonized standard exists. under the CRA, requiring a notified body to check conformity, and develop a harmonized cybersecurity standard for inverters to test against.
- Extend the RfG so that owners must use installers with verifiable minimum cybersecurity qualifications, and set a common 1 MW threshold for NIS2 and the Network Code on Cybersecurity, so every utility-scale plant falls clearly in scope.
- Control internet traffic from utility-scale inverters by documenting, encrypting, and authenticating all data. Communication should be outbound-only to whitelisted servers in the EU or equivalent jurisdictions, with no inbound communication permitted from outside the local network.
- Replace automatic manufacturer-triggered firmware updates with controlled manual updates installed by qualified maintenance providers.
- Restrict components and software from suppliers subject to the jurisdiction of third countries identified as posing significant cybersecurity risks, drawing on criteria in the proposed revised Cybersecurity Act.
These regulatory changes would create a stronger baseline, but harmonized standards and legislative changes take years. Meanwhile, owners and EPCs are signing specifications today for plants that will run for 20 years or more.
What Withthegrid recommend asset owners to do already
Setpoints from TSOs, DSOs, and traders all enter a plant through its controller. A single command can affect every inverter on site, making the controller one of the most sensitive targets on a solar park, but also the component where owners can close some attack routes.
We engineered our controller, the Teleport Gateway, around these exact constraints. It operates as an independent, secure barrier protecting your grid connection:
- The Teleport acts as an outbound-only device, communicating exclusively with our EU-based cloud. It accepts no inbound connections, so the device exposes no login page, VPN endpoint or management interface.
- Each unit authenticates using its own unique certificate based on asymmetric cryptography.
- We manage the firmware remotely. Updates are signed, verified at boot, and restricted during active asset control to protect system integrity. This is how we handle the trade-off the services describe between patching fast and keeping systems stable: updates are blocked while a schedule is active on an asset, or while a control strategy runs outside its agreed maintenance window.
- Our monitoring watches the device, the connected assets and the control loops 24/7.
- If connectivity fails, the Teleport relies on its local control logic. It continues enforcing the plant’s grid connection limits and local strategies independently of the cloud.
A controller at the grid connection has limits. If an attacker exploits a vulnerability in an inverter’s firmware, a controller like the Teleport cannot stop that inverter from switching off. Local network security also remains a shared responsibility: while the Teleport filters insecure local protocols, the owners must follow our configuration guidelines so those protocols are never exposed to the internet.
The Teleport is one layer in the "defense in depth" the AIVD recommend,See: Ministerie van Binnenlandse Zaken en Koninkrijksrelaties. (2026, October 7). Cyberadvies edge devices structureel doelwit van Chinese cyberactoren [Cyber advisory: Edge devices structural target of Chinese cyber actors]. AIVD. alongside segmentation, MFA and intrusion detection on the site network. Their advice on vendor diversity applies here too: when the controller, the firewall and the inverters come from different suppliers, an attack method built for one product line does not open every layer.
Regardless of your asset hardware choices, you can execute these six steps today:
- Scan your digital footprint and confirm that the devices answering from the public internet are the ones you expect, and nothing else. Forgotten devices are the riskiest: they may carry exploitable vulnerabilities or weak credentials that nobody is watching. Keep an inventory of every edge device on each site, who manages it, and which of its functions face the internet; management interfaces should not be publicly exposed. For devices that must stay exposed, monitor them, centralize their logs, patch them on a schedule, and protect every access route with strong authentication.
- Require every party with remote access to provide a complete list of endpoints their equipment connects to. Block all undocumented communication and segment the network so each supplier can reach only the systems it needs.
- Remove shared and default credentials. Use certificate-based authentication for system links and MFA for personnel. Monitor logins and access attempts, and send those records to the central log store.
- Send logs from firewalls, VPN gateways and plant controllers to a central store in a separate network segment, out of reach of anyone who compromises the device itself. AIVD and MIVD recommend keeping them for at least six months, preferably a year or longer.
- Agree in writing with every supplier and maintenance provider how fast security updates reach their equipment, who decides when an update goes in during operation, and how they support you during an incident. Then plan for an attacker who is already inside: select an incident-response partner before you need one and ensure they can access the logs.
- Mandate outbound-only communication and EU-based endpoints in your next tender specifications. Ask suppliers of edge devices and controllers for evidence of independent security testing and a software bill of materials.
Digitally, solar assets (and other asset types such as wind turbines and BESS) are currently fragmented and exposed. While regulatory alignment will take years to close the gaps across the continent, you can already take the first steps to fix the exposure on your own sites.